The Glitch


The Glitch

Overview: An installer plans to use a low mass boiler with several heating zones and an indirect water heater. Fearing burner short cycling, he adds a buffer tank, and pipes it all together as shown below.

Exercise: Can you spot at least five details that are incorrect?
 

The Fix

The Fix

To say this system is a piping aberration is going easy on it.

1. The indirect water heater should not interact with the buffer tank when it needs heat. The indirect tank has sufficient thermal mass of its own to prevent boiler short cycling. Even if the zone valve leading to the indirect opens when the tank aquastat calls for heat there would be very little flow through the tank. Most of the flow created by the buffer tank circulator would just do a U-turn at the closely spaced tees and head back into the buffer tank.

2. When it operates, the boiler circulator would create differential pressure between the headers at the top of the schematic. Although the zone valves would likely not bleed hot water to their zones when closed, it is very likely there will be unexpected flow into the two zones using circulators. The forward opening resistance of their check valves would not be able to hold back the differential pressure created by the boiler circulator.

3. The boiler circulator is pumping toward the expansion tank connection point. It should be pumping away from this point.

4. The circulators are shown with their inlet very close to the supply header. There should be at least 12 pipe diameters of straight pipe leading into the circulators.

5. There is no differential pressure bypass valve shown on the headers serving the zone valves.

6. The left-most zone circuit will not be able to draw heated water from the buffer tank.

7. Although the heat exchanger of the indirect tank has its inlet at the top and outlet at the bottom, the temperature gradient inside the tank is inverted. This would imply upside down temperature stratification, and nature is not going to allow that. (Just seeing if you’re paying attention.)

The fix drawing shows all corrections to the above problems.

The indirect water heater is piped as a separate circuit, and would likely operate with priority control.

Upon a call for space heating, the system’s controls check to see if the buffer tank is sufficiently warm to serve as the heat source. If so, the boiler is not fired, the boiler circulator remains off, and the buffer tank circulator operates. When the buffer tank has cooled through its differential, the boiler fires and the boiler circulator operates. The buffer tank circulator remains on. Heated water is supplied to the active zone(s), and any access heat is routed to the buffer tank, causing its temperature to rise. If the buffer tank climbs back up to its upper temperature setting the boiler and boiler circulator are turned off, and the above sequence repeats itself.

A spring-load check valve at the top outlet of the buffer tank helps prevent heat migration.
 

Links

Did you enjoy this article? Click here to subscribe to receive Radiant and Hydronics eNewsletter twice a month, delivered right to your inbox. 

Recent Articles by John Siegenthaler, P.E.

You must login or register in order to post a comment.

May 2009 Glitch & Fix

Dr. Dew
June 5, 2009
#1 The PDF Format link (232 kb) does not work #2 I knew that this Glitch was identical or similar to a previous one. Nov. 2007 is a close cousin Keep up this interesting series

PDF now working

site manager
June 8, 2009
Sorry for any inconvenience ... The PDF is now working properly.

Circulator Locations

Mike in Pittsburgh
May 2, 2012
Should the circs for the indirect and the boiler be on the cold side of the boiler and then the fill and expansion assebly be upstream of them?

Multimedia

Videos

Image Galleries

2013 QSC Power Meeting XXXVIII

March 14-16, 2013, San Diego

Photos by Kelly Faloon/Plumbing & Mechanical

4/18/13 2:00 pm EDT

Smart Pumping -- The "New Normal" in Hydronics

This webinar will explain the benefits these circulators offer, and show you how to best apply them in residential and light commercial hydronic systems. It will cover both basic and unique applications for the Bell & Gossett VARIO and AUTO circulators. Why not make the “hydraulic efficiency” of your systems on par with their thermal efficiency. This webinar will show you how to do it.

Radiant and Hydronics eNews

august cover

2013 August

In the August edition of Radiant & Hydronics, read about new technology in measuring energy, NASCAR driver Ryan Newman and State Water Heaters new partnership and Bradford White's newest apps. Also check out the latest products in the heating and cooling industry.

Table Of Contents Subscribe

Trade Associations

Are trade association memberships and participation beneficial to your company?
View Results Poll Archive

The Radiant and Hydronics Store

M:\General Shared\__AEC Store Katie Z\AEC Store\Images\radiant hydronics\HydronicsKnowHowII_CD.gif
Hydronics Know How II CD

The Hydronics Know How II CD contains all the columns and articles John Siegenthaler has written for Plumbing & Mechanical and PM Engineer, from the very first in July 1996 through December 2008. That’s over 200 articles and columns covering everything from heat loss to hydraulic separation.

More Products

Clear Seas Research

Clear Seas ResearchWith access to over one million professionals and more than 60 industry-specific publications, Clear Seas Research offers relevant insights from those who know your industry best. Let us customize a market research solution that exceeds your marketing goals.

Radiant Flooring Guide

Radiant flooring guide 2013Your Guide to suitable floor coverings and submaterials for use with radiant heating. CLICK HERE to read the latest edition of Radiant Floring Guide.

STAY CONNECTED

Facebook logo Twitter logo    YouTube logo      linkedin_40px.png