The Fix
What’s wrong?
1.
The zone valves should be located on the supply side of the zone circuits to
eliminate heat migration into inactive zone circuits.
2.
The tee shown below the zone valves is a “bullhead” tee. When both zones are
on, return flows slam directly into each other. This creates turbulence and
noise. It also wastes circulator head.
3.
There should be at least 12 diameters of straight pipe leading into the
circulator. Placing it close to the side port of the bullhead tee allows
turbulent flow into the circulator. This decreases circulator performance and
creates noise.
4.
The circulator in The Glitch drawing is pumping
toward rather than away from the expansion tank. This
causes a decrease in pressure within the zone circuits when their circulators
operate.
5.
There is no provision for differential pressure control in the original system.
6.
There are no purging valves in the original system.
These
glitches have been corrected in the fix drawing.