The Fix
The vast majority of geothermal water-to-water heat pumps are
single-speed “on/off” devices. When on, they produce heat output at or near
their rated output (depending on the exact entering temperatures and flow rates
on both sides of the heat pump). There is very little thermal mass in a heat
pump to store any heat that’s produced but not immediately sent to the load.
The
distribution system shown is zoned with valves, and thus flow rates and rates
of heat delivery can change drastically as the zones turn on and off. This will
almost surely cause “out of range” operating conditions within the
refrigeration circuit of the heat pump, leading to internal safety switch trips
(or worse).
To stabilize the situation, it’s imperative to
include a well-insulated buffer tank between the heat pump and the zoned
distribution system as shown in the fix drawing. The heat pump cycles on and
off based on the setpoint temperature of the buffer tank and the temperature
differential across which the tank needs to operate. The load circuits can now
operate completely independently of the on/off cycling of the heat pump.
Other
errors in the original design include:
- The lack of air
separation on both sides of the heat pump.
- The lack of an
expansion tank on both sides of the heat pump.
- Lack of
differential pressure control on zoned distribution system.
- Failure
to provide counter flow through the evaporator (earth loop) side of the heat
pump.
- Failure to route the coolest water (leaving heat pump
evaporator) through the upper portion of the horizontal earth loop.
Details
that correct these conditions are shown in the fix drawing.