The Fix
A four-way motorized mixing valve is
specifically design to create two mixing points within itself: one to regulate
system supply temperature and the other to boost boiler inlet temperature high
enough to prevent sustained flue gas condensation. To accomplish the latter,
the controller operating the valve’s motor must sense and react to boiler inlet
temperature.
Thus,
a boiler inlet temperature sensor is required and is shown in the Fix drawing.
Although
a primary/secondary system would work, there are simpler and less costly
methods to achieve hydraulic separation between the circulators when the boiler
and header piping have low flow resistance. With relatively short and
generously sized header piping between the boiler and four-way valve,
sufficient flow will be created by the combined effects of buoyancy and
momentum exchange within the valve.
Eliminating
the primary loop circulator reduces both installation and operating cost. It
also eliminates reduced water temperature to the indirect water heater coil if
the space-heating subsystem is active, and the water heater is not operated as
a priority load.
Did
you notice that the primary loop circulator is pumping
toward rather than away from
the location where the expansion tank connects to the system? That’s definitely
incorrect. So is the placement of the secondary circulator serving the indirect
water heater. Secondary circulators should always direct water
into the secondary circuit. This
treats the upstream tee of the closely spaced pair as the point of no pressure
change for the secondary circuit. Pressure within the secondary circuit goes up
when its circulator is operating.
The
supply temperature sensor is located immediately downstream of the four-way
mixing valve in the Glitch drawing. Although mixing has begun by the time flow
passes this sensor location, it may not be complete and the sensor may not be
sensing the final blended temperature supplied to the manifold station. It’s
always good practice to install the supply temperature sensor downstream of the
distribution circulator to ensure complete mixing has occurred before flow
passes the sensor.
Finally,
purging valves have been added to the return ends of both load circuits.
By: rjm
Posted: January 23, 2012 10:34 PM
By: Todd Davis
Posted: February 1, 2012 11:32 AM
By: c. shoff
Posted: February 17, 2012 1:31 PM
There also need to be an isolation valve on the discharge side of the return manifold with a drain valve between it and the manifold. This allows for "power" purging of the radiant floor. In addition, once purged the isolation valve provides isolation when a pump or other serviceable item needs to be changed.