The Fix
In order for a hydraulic separator to
achieve its goal, headers leading to the individually pumped load circuits must
be generously sized (design flow velocity of 2 ft. /sec or less). If not, a
significant pressure drop can develop along the length of both the supply and
return headers. This pressure drop will cause some interference among the zone
circulators. It’s not the fault of the hydraulic separator, but rather the
headers connected to it. This is also true on the boiler side of the separator.
When the header is generously sized
there is no need for reverse return piping. The latter is appropriate when the
same circulator supplies flow through several parallel piping circuits having
similar flow requirements. This is
not
the way this system is configured. Why waste piping when it’s unnecessary?
Another problem involves the indirect
tank connected on the boiler side of the hydraulic separator. In this
arrangement, the sensor for the multiple-boiler controller is not getting a
good indication of the water temperature going to the load during the
prioritized domestic water heating mode, and thus cannot control it properly.
This has been corrected by moving the connections for the indirect tank
downstream of the supply temperature sensor.
The coil heat exchanger inside the
indirect water heater is also piped backwards. Hot water from the boilers
should always enter the top of the coil to create counterflow heat exchange
within the tank.
Other errors / omissions
include:1. Lack of purging valves on the zone circuits
and indirect circuit.
2. Circulators piped too close to the header
(and thus receiving turbulent flow into the impeller). There should be at least
12 times the pipe diameter of straight piping leading into circulators.