The Fix
Although a mod/con boiler can be
used in this type of system, it will operate at elevated temperatures
(depending on the load supplied by the baseboards versus that supplied by the
low temperature zones). Under partial load conditions, the boiler’s inlet water
temperature may be low enough to allow some condensing mode operation.
Although the installer’s intention
was to create a “primary loop,” that’s not what he ended up with. The two high-temperature
zones are piped across the loop rather than into pairs of closely spaced tees. The
“primary circulator” will also induce hot water migration into the higher
temperature zones due to the head loss around the remainder of the “primary
loop.”
Another problem is the lack of a
thermal trap, or check valve to stop heat migration through the injection
risers when the injection pump is off, but the “primary circulator” is
operating. Although the drop leg in the piping might constitute a “trap” of
sorts, it will not stop heat migration into the injection risers.
There is no need to create a primary
loop in this system. Provided the headers are relatively short and generously
sized (flow velocity less than 4 feet per second with all circulators running),
the injection pump can be piped across the headers as shown in the fix drawing.
However, be sure that a check valve is used in the injection circulator.
There should also be purging valves
on the return side of all zone circuits, and these valve need to be installed
in the correct orientation. The glitch drawing shows them upside down on the
return side of the high temperature zones.
There is no air separator in the
glitch drawing. The fix drawing shows the air separator installed, so flow
leaving the boiler passes through it in both space heating and domestic water
heating modes.
The boiler’s supply temperature
sensor is mounted too close the closely spaced tees. In this position, the
mixing between the incoming boiler water and system bypass water is not
complete, and the temperature has not settled to the final blended value
supplied to the distribution system. Ditto for the supply sensor of the
injection mixing controller. The controls will respond to incorrect
temperatures.
There is no need for the injection
mixing controller to sense boiler return temperature with a condensing capable
boiler.
Finally, a ball valve is not a good
choice for balancing the return injection riser. A globe valve or other valve
specifically intended for balancing should be used.