The Fix
It’s almost
never a good idea to pipe heat sources in series. Doing so creates additive
flow resistance, and creates the potential for incompatibilities in operating
temperature. It also allows the inactive heat source to act as a heat
dissipater.
The two
circulators operating simultaneously needlessly add to electrical operating
cost. When only one zone is operating,
there may still be a chance the heat pump would be operating with insufficient
flow, and trip out under a high head pressure condition.
Beyond these
aberrations is a valved distribution system without differential pressure
regulation. The expansion tank is incorrectly located near the discharge side
of a circulator. The earth loop lacks an expansion tank and air-separating
device. The indirect water heater at the far end of the headers also creates
more heat loss than necessary from the headers. Hot water produced by the
boiler will also have flow through the heat pump’s condenser during the water
heating mode.
The corrected
schematic places the boiler and heat pump so each can serve as the system’s
heat source without affecting the other. The heat pump delivers heat to a
buffer tank, which in turn delivers heat to the zoned distribution system. This prevents the heat pump from short
cycling under low load conditions. A pressure-regulated variable speed
circulator controls differential pressure in the distribution system. An air
separator, expansion tank and valving for adding fluid have been added to the
earth loop.
Although some
earth loops operate without this trim, having it in place limits pressure
variations and helps the earth loop clear itself of air for the quietest
possible operation. Domestic water is treated as a priority load, and is only
served by the boiler.
By: Fred
Posted: May 15, 2009 4:53 PM