The Fix
A geothermal
heat pump and boiler can be used together in the system. The original plan does
allow the possibility of the modulating boiler adding heat to the flow leaving
the heat pump. However, a typical geothermal heat pump and low mass mod/con
boiler can both generate substantial flow resistance, which would add together
if they were connected in series as shown. This could severely bottleneck flow
to the point of causing operational problems with both the heat pump and
boiler.
Furthermore,
there’s no way to bypass flow around either the boiler or heat pump when either
is inactive. Thus, if either heat source is inactive while the other is
operating, the inactive heat source becomes a heat dissipater. Thus the series
piping arrangement is not recommended.
The original
design will likely subject the heat pump to short cycling when only one or two
zones are active. A buffer tank has been added to the fix drawing to stabilize
operation of the heat pump. In this case, the heat pump operates to maintain
the buffer tank within a set temperature range. The buffer tank then becomes
the heat source to the system when its circulator is turned on.
In the fix
drawing, the two heat sources (boiler and buffer tank) are piped in parallel.
They can operate independently, each with their own circulator, or they could
operate simultaneously in low temperature space heating mode.
A typical
geothermal heat pump is limited to a supply water temperature of about 120ºF. Although this may be fine for low
temperature radiant heating, it will not be high enough for domestic water
heating via an indirect water heater. Thus the boiler will handle the DHW load.
In the fix drawing, this is enabled by a separate circulator. Upon a call for
domestic water heating, the boiler goes to an elevated setpoint temperature,
the DHW circulator turns on, and the boiler’s space heating circulator turns
off. If necessary, the heat pump could supply space heating during this mode.
Another problem
with the original design is that there is no means of differential pressure
control in the original schematic. This has been addressed in the fix through
use of a variable speed pressure-regulated circulator.
Finally, the original design has no central air
separator. It also shows an unvented high point in the piping leading into the
heat exchanger of the indirect tank.